Technical Data

    System Supply
  • Auxiliary Supply 90 – 270 VAC/ DC
    Frequency
  • Frequency 50 Hz / (60Hz) ± 3%
    Power Consumption
  • Power Consumption 8 VA max.
    Output Relay Contacts
  • Output Relay Contacts2 CO
    Output Contact Rating
  • Output Contact Rating5 Amp, 240 VAC [RESISTIVE]
    Monitoring ( Software Selectable)
  • Monitoring ( Software Selectable)Phase To Phase Voltages Or Phase To Neutral Voltage
    Power On Delay
  • Power On Delay 3.5 ± 1.5 Sec.
    Settings
  • SettingsBy Means Of Keyboard [4 Keys]
    Setting Parameters & Trip Level
    3 PH. 3 W (System Supply - 415 VAC PH - PH)
PARAMETER SPECIFICATION RESOLUTION FACTORY SETTING
NOMINAL MONITORING VOLTAGE 380 / 415 / 440 VAC [Ph-Ph] N.A. 415 VAC [Ph-Ph]
UNDER VOLTAGE 1 TO 80 V BELOW NOMINAL VOLTAGE  1 V 60 V
OVER VOLTAGE 1 TO 60 V ABOVE NOMINAL VOLTAGE 1 V 50 V
UNBALANCE 1 TO 20 % OF AVERAGE MONITORING VOLTAGE 1% 10%
INDIVIDUAL TRIP DELAY FOR UV, OV, UB FAULTS 1 TO 59 SECOND OR 1 SEC. 3 SEC
1 - 5 MINUTE 1 MIN.
UV, OV, UB, RP PROTECTION BYPASS YES / NO N. A. NO
RESET AUTO / MANUAL N.A. MANUAL
PASSWORD 00 TO 99 [TWO DIGITS] 1 3
FACTORY SET YES / NO N. A. NO
    3 PH. 3 W (System Supply - 110 VAC PH - PH)
PARAMETER SPECIFICATION RESOLUTION Factory Setting
NOMINAL MONITORING VOLTAGE 110 VAC [Ph-Ph] N.A. 110 VAC [Ph-Ph]
UNDER VOLTAGE 1 TO 15 V BELOW NOMINAL VOLTAGE  1 V 15 V
OVER VOLTAGE 1 TO 35 V ABOVE NOMINAL VOLTAGE 1 V 20 V
UNBALANCE 1 TO 20 % OF AVERAGE MONITORING VOLTAGE 1% 10%
INDIVIDUAL TRIP DELAY FOR UV, OV, UB FAULTS 1 TO 59 SECOND OR 1 SEC. 3 SEC
  1-5 MINUTE 1 MIN.  
UV, OV, UB, RP PROTECTION BYPASS YES / NO N. A. NO
RESET AUTO / MANUAL N.A. MANUAL
PASSWORD 00 TO 99 [TWO DIGITS] 1 3
FACTORY SET YES / NO N. A. NO
    3 PH. 4 W (System Supply - 415 VAC PH - PH)
PARAMETER SPECIFICATION RESOLUTION FACTORY SETTING
NOMINAL MONITORING VOLTAGE 220 / 230 / 240 / 250 VAC [Ph-N] 10 V 230 VAC [Ph-N]
UNDER VOLTAGE 1 TO 50 V BELOW NOMINAL VOLTAGE  1 V 40 V
OVER VOLTAGE 1 TO 25 V ABOVE NOMINAL VOLTAGE 1 V 20 V
UNBALANCE 1 TO 20 % OF AVERAGE MONITORING VOLTAGE 1% 10%
INDIVIDUAL TRIP DELAY FOR UV, OV, UB FAULTS 1 TO 59 SECOND OR 1 SEC. 3 SEC
1 - 5 MINUTE 1 MIN.
UV, OV,UB, RP PROTECTION BYPASS YES / NO N. A. NO
RESET AUTO / MANUAL N.A. MANUAL
PASSWORD 00 TO 99 [TWO DIGITS] 1 3
FACTORY SET YES / NO N. A. NO
    3 PH. 4 W (System Supply - 110 VAC PH - PH)
PARAMETER SPECIFICATION RESOLUTION Factory Setting
MONITORING VOLTAGE 63 VAC [Ph-N] NA 63 VAC [Ph -N]
UNDER VOLTAGE 1 TO 15 V BELOW NOMINAL VOLTAGE  1 V 15 V
OVER VOLTAGE 1 TO 25 V ABOVE NOMINAL VOLTAGE 1 V 20 V
UNBALANCE 1 TO 20 % OF AVERAGE MONITORING VOLTAGE 1% 10%
INDIVIDUAL TRIP DELAY FOR UV, OV, UB FAULTS 1 TO 59 SECOND OR 1 SEC. 3 SEC
1-5 MINUTE 1 MIN.
UV, OV, UB, RP PROTECTION BYPASS YES / NO N. A. NO
RESET AUTO / MANUAL N.A. MANUAL
PASSWORD 00 TO 99 [TWO DIGITS] 1 3
FACTORY SET YES / NO N. A. NO
    Test Facility
  • Test FacilitySimultaneous Press Of Esc & Up Keys.
    Reverse Phasing Trip Delay
  • Reverse Phasing Trip Delay Instantaneous (Less Than 1 Sec.)
    Setting Accuracy
  • Setting Accuracy± 2 % Of Set Parameter
    Time Accuracy
  • Time Accuracy± 5 % Of Setting
    Display
  • DisplayLcd [16 X 2 Char. Type With Backlit]
    Display Voltage Resolution
  • Display Voltage Resolution 1 Volt
    Display Accuracy
  • Display Accuracy± (1 % + 5 Digits) Of Nominal Voltage
    Resetting
  • ResettingAuto / Manual [simultaneous Press Of Up & Down Keys]
    Reset Gap For Auto Reset Facility
  • Uv Reset Gap3 % ± 1 % Of Trip Setting.
  • Ov Reset Gap3 % ± 1 % Of Trip Setting
  • Unbalance Reset Gap20 % ± 5 % Of Trip Setting
    Led Indications
  • P. On (Green)Power On
  • Ov (Red)Over Voltage
  • Uv (Red)Under Voltage
  • Ub/sp (Red)Unbalance / Single Phasing / Reverse Phasing
    Enclosure
  • Enclosure96 X 96 Type Enclosure
    Dimensions
  • Overall [mm] 96 X 96 X 80 Mm [h X W X D]
  • Cutout [mm] 92 X 92 [+ 1/– 0] Mm
    Mounting
  • MountingFlush Mounting
    Operating Conditions
  • Temperature0° To 60° C
  • HumidityUp To 95% Rh
    Weight [gms.]
  • Weight [gms.]800 (Approx.)
    Optional Feature
  • Optional FeatureRs232 Pc Interface With Minilec Exclusive Windows
    Based Pc Side Software.

Applications

Inverter

UPS

Auto Mains Failure Panels.

Battery Charger Panel

DC Drive Control panels.

DG Set Panel

Connect with us