Voltage Monitoring Relays
Frequency Monitoring Relays
Power Monitoring Relays & CBCT
Level Controllers – Conductive Liquids
Level Controllers – Non Conductive Liquids

Monitoring Relays

S2 VMR5

S2 VMR5 Monitoring Relays - Minilec group

Technical Data

    Supply Voltage
  • System Supply 100-120/220-240/380-440V AC -25%+20%,48-63 Hz
    Output Relay Contact
  • Output Relay Contact 1 CO + 1 CO / 2 CO
    Trip Setting
  • Under Voltage Ph N Sensing:
    For 380-440V AC : 165-245V AC (Variable)
    For 220-240V AC : 95-135V AC (Variable)
    For 100-120V AC : 45-65V AC (Variable)
  • Over Voltage Ph N Sensing:
    For 380-440V AC : 230-310V AC (Variable)
    For 220-240V AC : 130-170V AC (Variable)
    For 100-120V AC : 60-80V AC (Variable)
    Trip Time Delay
  • Trip Time Delay 1-10 Sec (Variable)
    Power on Delay
  • Power on Delay 1-10 Sec (Variable)
    Reset
  • Reset Auto / Manual Reset
    Weight
  • Weight 110 gms. (Approx)
    Dimensions (mm)
  • Overall (L x W x D) 90 x 35 x 60
  • Mounting 35 mm rail Mounting
    Note:
  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)

Applications

Battery Charger Panels.

Generator Set Panels.

Auto Mains Failure Panels.

Inverter Panels.

DC Drive Control panels.

UPS