(LIKELY TO BE DISCOUNTINUED)
  • Phase Failure, Unbalance
  • Phase Sequence, Under voltage
  • Over Voltage, Manual Reset
  • Fixed Unbalance setting
  • Adjustable UV/OV settings
  • 2 CO output relay
    Supply Voltage
  • System 100-120/220-240/380-440 VAC±20%, 3Ph-3Wire
  • Auxillary Built In
    Output Contacts
  • Output Contacts2 CO
    Trip Setting(Volts)
  • Phase SequenceYes
  • Phase Unbalance10% fixed
  • Under VoltageFor 380-440V AC
    For 220-240V AC
    For 100-120V AC
    285-425V AC [Variable]
    165-225V AC [Variable]
    75-115V AC [Variable]
  • Over VoltageFor 380-440V AC
    For 220-240V AC
    For 100-120V AC
    400-520V AC [Variable]
    230-290V AC [Variable]
    105-140V AC [Variable]
    Trip Time Delay
  • On Phase Failure 3.5 secs ± 1.5 sec.
  • On UV/OV 3.5 secs ± 1.5 sec.
    Resetting Mode
  • Resetting Mode Auto
    Weight
  • Weight430 gms.
    Dimensions (mm)
  • Overall (L x W x D)76 x 30.5 x 117.5
  • Mounting (L x W)68 centre to centre / 35 mm rail Mounting
    Note:
  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
  • * CE marked products available on request.

Suitable for monitoring 3 Ph. System supply from MAINS & used by motor load:

  • AC & R Chiller compressor motors
  • AHU Fan /Pump Motors
  • Machinery using multiple small motors
  • MAIN powers supply distribution panel board
  • DG Set application
  • UPS
  • Submersible Pumps
  • Hoist & Crane