• Single Phase Under & Over voltage,
  • Auto Reset,
  • Adjustable under / over voltage settings,
  • 2 CO output relay
    Supply Voltage
  • System Supply 220/230/240 V AC (+ 20% - 30%), 50/60 Hz
    Output Contacts
  • Output Relay Contacts2 CO
    Trip Setting(Volts)
  • Under Voltage75 - 95% [Variable] of set value
  • Over Voltage 105 - 120% [Variable] of set value
    Trip Time Delay
  • Trip Time Delay2- 5 Sec (Fixed) (UV/OV)
    Power on Deley
  • Power on Deley
    Reset
  • Reset Auto Reset
    Weight
  • Weight180 gms.
    Dimensions (mm)
  • Overall (L x W x D)76 x 30.5 x 117.5
  • Mounting (L x W)68 centre to centre/ 35 mm rail Mounting
    Note:
  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)

Relay contact position shown in 'Power off' condition

  • Battery Charger & Float Charger Panels.
  • Telecom Power Supply Units
  • UPS for Office Computers

All Products