| MBAS 0600 is a improved version of earlier MBAS 9400, and is available for 4 to 32 windows |
| |
| The Functional Features |
|
Fixed Sequence ( S1/S2/S3/S4) |
|
Potential free dry contact inputs |
|
NO/NC inputs selectable configuration |
|
Relay output for external Audible
Hooter 3rd Relay optional for either of
below mentioned features
a) Ring back hooter
b) Supervisory control |
|
Minilec Standard Communication
Protocol |
|
| |
| The Design Features |
|
Single chip microcontroller logic |
|
Opto isolated inputs and outputs |
|
Super Bright LED window illumination |
|
High Noise immunity / isolation |
|
Switch mode power supply |
|
Self surveillance watchdog LED |
|
|
| The Constructional Flexibility |
|
Conforming to DIN panel cutouts |
|
Replaceable snap-on window capsules |
|
Two different window size |
|
Molded enclosures |
|
| |
| Optional Features |
|
Any custom built operating sequences |
|
Manned / Unmanned function |
|
MODBUS RTU/ASCII Protocol |
|
Fault Follower contact output per fault Input (NO or NC) |
|
Supply fail indication / annunciation Built in |
|
Built-in control push buttons |
| Supply Voltage |
: |
24 / 30 / 48 / V DC, 20-60 V AC/DC, 90-270 V AC / DC |
|
| Windows |
: |
4 / 6 / 8 / 12 / 16 / 18 / 22 / 24 / 32 |
|
| Window Sizes |
:
|
30 x 30mm / 30 x 65 mm |
|
| Display Device |
: |
Super bright high efficiency low power consuming LED's |
|
| Facia Type |
: |
Individual windows Front Replaceable |
|
| Window/LED Colours |
: |
RED, Yellow, Green, White & Blue |
|
| Flash Rate |
: |
Fast - 60 flashes/min. Slow - 30 flashes/min. |
|
| Response Time |
: |
40 msec. |
|
| Input Signal |
: |
Potential free contacts (NO or NC site selectable) |
|
| Grouping |
: |
Trip / Non Trip site selectable |
|
| Interrogation Voltage |
: |
+ 12 V DC |
|
| Output Contacts |
: |
1 NO + 1 NO + 1 NO (optional) |
|
| Architecture |
: |
Integrated |
|
Operational Sequences
(site selectable) |
: |
Auto/Manual/First-up/Ringback (optional)
OR any other sequence on request |
|
| Operational Temp. |
: |
0-60 degrees C |
|
| Power Consumption |
: |
1.5 Watts per Window (Max) |
|
| Optional |
: |
AC-DC fail Annunciation or Indication / Repeat Relays / RS232 - 485 Port |
|
Dimensions (mm)
|
Panel Cutout (L x W) |
|
Overall (L x W x D) |
|
:
:
: |
| 1D |
2D |
3D |
4D |
| 138 x 68 |
138 x 138 |
138 x 210 |
138 x 282 |
| 144 x 72 x 215 |
144 x 144 x 215 |
144 x 216 x 215 |
144 x 288 x 215 |
|
| Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) * CE marked products available on request. |
|
| Note |
|
In Case of Normal Supply Failure, RLY-3
is for Stand by Hooter (at AC/DC fail
feature) |
|
For supply fail Annunciators/Indication,
Window no. 01 is dedicated. |
|
External SMPS is provided for different
supply voltages. |
|
| |
| Part names & locations |
Dimnesional & Panel Cutout Details |
 |
 |
|
| |
|
|
|
| Functional Block Diagram |
Connection Diagram
(FOR MAX. 32 POINT MBAS 0600.) |
 |
 |
|
Note |
|
In Case of Normal Supply Failure, RLY-3
is for Stand by Hooter (at AC/DC fail
feature) |
|
For supply fail Annunciators/Indication,
Window no. 01 is dedicated. |
|
External SMPS is provided for different
supply voltages. |
|
|
| |
|
| |
|
Suitable for Panels in Following Apllications:
|
Suitable for Process Plant, |
|
Plants, Diesel Generators, |
|
Control Rooms, |
|
C & R Panel |
|
Material handling Systems |
|
Instrumentation Panel |
|
Battery Charger panel |
|
Compressor control panel |
|
| |
|
|