An Integrated approach to Excellence  
Products >> Phase Failure Relays >> Phase Failure Relays - Multi Function >> HLS D2

HLS D2
FAQs How to Use Enquiry
Introduction:
It is a Negative Sequence Voltage Sensing Phase Failure with Under & Over Voltage Relay. It is best suitable for 3 phase loads or 3 phase motor / pump loads only. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in DIN Rail mounting enclosure.
Features:
· Under & Over Voltage (Factory Set).
· Monitors Aux.Voltage for Under & Over Voltage.
· Monitors all 3 phases of Voltage Supply for Unbalance & Phase Loss.
· Available for any System Voltage.
· Auto Reset.
· Sleek DIN Rail mounted enclosure.
Application Areas:
Measures 3-Phase supply for Unbalance Voltage, Loss of Phase, Phase Sequence, Under Voltage & Over Voltage. Best suitable for balance 3 phase loads or motor loads only. Phase failure &UV/OV Relays can be best used for a host of Auxiliary Systems & Plant control panels & machinery.
Technical Specifications:
Sr.
Parameter
Specifications
1 Supply Voltage System 240 / 380 / 415 / 440 V AC ±20%; Auxiliary 110 / 240 / 380 / 415 / 440 V AC ±20%
2 Output Contacts 1 CO
3 Trip Setting (Volts) Phase unbalance 40 V ±6 V (fixed); Under Voltage 80% ± 5 V (fixed); Over Voltage 120% ± 5V (fixed); Water Level N.A.
4 Trip Time Delay On Phase Failure 3.5 secs. ± 1.5 sec; On UV/OV Less than 2 secs.
5 Resetting Mode Auto
6 Weight 400 gms.
7 Dimensions (mm) Overall (L x W x D) 76 x 56.5 x 117.5; Mounting (L x W) 67 x 46