| Introduction: |
| It is a Pump Protection Relay. It offers protection against overloading, underloading apart from protection against Phase Failure, Phase Unbalance, Phase Sequence Faults & Dry Running Protection. It is best suitable for individual 3 phase Submersible Pump Protection rated upto 80 A. It eliminate conventional bimetal (thermal) overload relay with superior protection level. It is used for Pumps with Current Sensor CTS. It is recommended for effective Motor Protections in Machine Tools, Compressors & Pumps. |
|
|
|
| Features: |
· Protects against Overload, Phase Loss, Reverse Phase Sequence & Dry Run.
· Selectable Dry Run setting 50% or 75%.
· 1 CO output contact, 5A / 230V AC (Resistive).
· Suitable with Minilec External current sensors & 5A CTs.
· Manual / Remote / Auto Reset.
· Panel flush mounted enclosure.
|
|
|
 |
|
|
|
| Application
Areas: |
| Submersible pump control panels
Air handling unit fans
Belt conveyors motor panels for zero speed sensing. |
|
|
|
| Technical
Specifications: |
|
|
|
|
|
Specifications |
| 1 |
Supply Voltage |
System 240/380/415 V AC
±20% 50/60 Hz ±3%; Auxiliary 110 / 240 / 380/ 415 V AC
±20% 50 / 60 Hz |
| 2 |
V A Burden |
— |
| 3 |
Input |
— |
| 4 |
Output Relay Contact |
1 CO |
| 5 |
Trip Setting |
Phase to phase unbalance 50% of I FLC; Under current (Dry running) 50% or 75% of I SET; Overload Above 120% of set current (IDMTL) |
| 6 |
Trip type delay |
On phase failure 5.5 secs ±1.5 secs.; For dry running 3.5 secs ±1.5 secs.; For overloading As per selectable inverse time Characteristics 2 - 10 secs. (variable) |
| 7 |
Resetting |
Automatic / Manual / Remote |
| 8 |
Temperature |
— |
| 9 |
Humidity |
— |
| 10 |
Dimensions (mm) |
Unit Overall (L x W x D) 96 x 96 x 76; Panel mounting (L x W) 92 x 92 |
| 11 |
Approx Weight |
425 gms. |
|