| Introduction: |
| It is a Phase Failure with Under & Over Voltage Relay. It is best suitable for protection of balanced 3 phase loads or 3 phase Motor / Pump loads only or for monitoring 3 phase MAINS supply. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in 11 pin Plug-in base mounting & flash mounting enclosure. |
|
|
|
| Features: |
· Under & Over Voltage (Adjustable).
· Monitors Aux.Voltage for Under & Over Voltage.
· Monitors all 3 phases of voltage for severe unbalance & phase loss.
· External Aux.Supply.
· Auto Reset.
· Panel Flush Mounted Enclosure.
|
|
|
 |
|
|
|
| Application
Areas: |
| Measures 3-Phase supply for Unbalance Voltage, Loss of Phase, Phase Sequence, Under Voltage & Over Voltage.
Best suitable for balance 3 phase loads or motor loads only.
Phase failure &UV/OV Relays can be best used for a host of Auxiliary Systems & Plant control panels & machinery. |
|
|
|
| Technical
Specifications: |
|
|
|
|
|
Specifications |
| 1 |
Supply Voltage |
System 240 / 380 / 400 / 415 V AC ± 20%, 50 / 60 Hz; Auxiliary Built-in |
| 2 |
Output Contacts |
1 CO |
| 3 |
Trip Setting (Volts) |
Phase unbalance 40 V ± 6 V (fixed); Under Voltage 190 V (fixed); Over Voltage 260 V (fixed); Water Level N.A. |
| 4 |
Trip Time Delay |
On Phase Failure 3.5 secs ± 1.5 sec.; On UV/OV 10 secs. |
| 5 |
Resetting Mode |
|
| 6 |
Weight |
430 gms. |
| 7 |
Dimensions (mm) |
Overall (L x W x D) 96 x 96 x 76 (flush mounting); Mounting (L x W) 92 x 92 (cutout) |
|