Introduction:
It is a Negative Sequence Voltage Sensing Phase Failure Relay. It is best suitable for 3 phase loads or 3 phase motor / pump loads only. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in DIN Rail mounting enclosure.
Features:
· Monitors all 3 Phases of Voltage Supply.
· Available for any System Voltage.
· External Aux.supply.
· Auto Reset.
· Sleek DIN Rail mounted Enclosure.
· 1 CO output contact.
Application Areas:
It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Air-conditioning & Pump Control Panels. It is available in DIN Rail mounting enclosure. Suitable for Agricultural pump set.
Technical Specifications:
Sr.
Parameter
Specifications
1 Supply Voltage System 240 / 380 / 415 V AC ±20%; Auxiliary 110 / 240 / 380 / 415 / 440 V AC ±20%
2 Output Contacts 1 CO
3 Trip Setting (Volts) Phase unbalance 40 V ±6 V (fixed); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A.
4 Trip Time Delay On Phase Failure/Seq. 3.5 sec. ±1.5 sec.
5 Resetting Mode Auto
6 Weight 320 gms.
7 Dimensions (mm) Overall (L x W x D) 76 x 30.5 x 117.5; Mounting (L x W) 68 centre to centre